Home   |   Contact Us   |   About Newtex  

Newtex Fire Curtains

Fully approved protection from fire, heat, and smoke

 Newtex Fire Curtain Newtex custom-made proscenium fire safety curtains are designed for use in theaters,stages, school auditoriums and other public performance areas. Mostcity and state-mandated building codes require the use of thesecurtains, which are lowered in the event of a fire on stage and protectaudiences against flames, heat, and smoke as the area is evacuated. Fabricated from asbestos-free ZetexPlus, our curtains have been tested to ensure they exceed nationally recognized model fire codes. 


Applications: New installations or replacement of existing asbestos or other curtains in proscenium theaters, stages, auditoriums, schools, and public performance areas

FEATURES:


• Listed and approved by the California State Fire Marshall (Listing No. 1670-1164:101) and New York City Department of
  Buildings (List Number MEA 212-08-M) for use as Proscenium Fire Safety Curtains. 
• Meet or exceed most national and local building codes, including IBC 2000, 2006; UBC 1991, 1994/97; SBCCI 1991,
  1997; BOCA 1991, 1994/96; Life Safety 1991, 2003
• Made from asbestos-free ZetexPlus, which resists fire, heat, and smoke
• Available with our without wire insertion
• Custom-made based on your stage dimensions and requirements
• Shipped fan-folded with mounting hardware for ease of installation 
• Available in tan or black

PRODUCTS:


Brail Type Curtains - Used when the space above the proscenium is half or less than the height of the proscenium
opening.  Stored accordion-folded above the proscenium.

Straight Lift Curtains
-
Simpler design used when the space above the proscenium is at least twice the height of the
proscenium opening.  Stored straight (without folds) above the proscenium.

ZetexPlus® Smoke Seals
- Designed to close the gap between the fire curtain and proscenium wall, preventing smoke
from escaping and reaching the audience.  

ZetexPlus® Borders
- Wrapped around stage lights to protect stage curtains from potential damage or risk of fire. 

Contact us if you are looking for a complete rigging solution, and we can recommend a trusted partner.

TEST PROCEDURES:


ZetexPlus fire curtains have been tested using the procedures below to ensure they meet or exceed most building code requirements for performance of proscenium fire curtains. 

PropertyTest Procedure
Fire EnduranceASTM E119 (UBC 43-1, NFPA 251, UL 263)
Flame Spread/Smoke Density
ASTM E84-89a (UBC 42-1, NFPA 255, UL 723)
Tensile Strength (Breaking Strength)ASTM D-1682-64

Tests were performed by Intertek Testing Services/Warnock Hersey, an approved test facility.  Listing agencies include the California State Fire Marshal's Office and New York City Department of Buildings.

FABRIC SPECIFICATIONS:


PropertyTest Procedure
Fire EnduranceASTM E119 (UBC 43-1, NFPA 251, UL 263)
Flame Spread/Smoke Density
ASTM E84-89a (UBC 42-1, NFPA 255, UL 723)
Tensile Strength (Breaking Strength)ASTM D-1682-64

Note:  Local building codes can vary, so understand your specific requirements before purchasing a fire curtain.